Description
Application & Control characteristic:
- Control and protect universal pump
- Adopting liquid probe, float switch or pressure switch to control pump start and stop
- Applied for water supply by liquid level control through float switch or liquid probe
- Applied for booster by pressure control through pressure switch and pressure tank
- Applied for drainage by liquid level control through float switch or liquid probe
- Applied for sewage pump with piggy-back float switch
Features:
- Pump last five faults record displaying
- Pump accumulative running time displaying
- Pump shaft anti-rust
- Present RS485 port
- Overflow alarm for drainage application
- Remote control panel (Optional)
- LCD screen displaying pump running status
- LCD screen locked function under auto state (Settable)
- Push button calibration
- Memory function when power off & recovery
- Signal transmission distance up to 1000m
- Pump start time delay (Time settable)
- Pump stop time delay (Time settable)
- WIFI module (Optional)
Specifications:
MODEL
L531
L931
Main technical data
- Start type
- Qty of controlled pump
- Rated input voltage
- Capacitor
- Rated output power
DOL (Direct on line)
Single Pump
AC380V/AC400 Three phase
0.75-4kw (1hp-5.5hp)
5.5kw-11kw (7.5hp-15hp)
15kw (20hp)
Max. Motor
Output at 380V 3Ph
Full Load
Max (A)
Starting Current Max (A)
HP
KW
1.0
0.75
12A
60A
1.5
1.1
2.0
1.5
3.0
2.2
5.0
3.0
5.5
4.0
7.5
5.5
25A
125A
10.0
7.5
15.0
11.0
20.O
15.0
32A
160A
Protection Function
- Overload protection
- Pump stalled protection
- Dry run protection with sensor free
- Under voltage protection
- Over voltage protection
- Repeat start protection
- Open phase protection
- Overload protection
- Pump stalled protection
- Dry run protection with sensor free
- Under voltage protection
- Over voltage protection
- Repeat start protection
- Phase unbalance protection
- Phase reversal protection
- Open phase protection
- Over temperature protection
Main installation data
- Working temperature
- Working humidity
- Degree of protection
- Mounting type
- Unit dimension (L x W x H)
-25°C-- +55°C
20%--90%RH, no drips concreted
IP54
Wall mounting
300× 240×120mm
SET/CTN Packing Size
6 sets/ctn 69*58*46cm
Connectable sensors
Liquid probe (standard accessory) / Float switch / Pressure switch