Tornatech GPD Diesel Engine Fire Pump Controllers
Description
- Designed to control Diesel Engine driven Fire Pumps
- Built to the latest NFPA 20 Standards, UL Listed and FM Approved
- Manual and Automatic Operation
- Built in Battery Chargers
- Pressure and event Recorder
Standard Features:
AC
- 120V/1ph/50-60hz
- 208V to 240V/1ph/50-60hz
DC
- 12VDC
- 24VDC
Grounding system: Negative
Battery chargers
- Two independent fully automatic
- 10A continuous charge
- 500mA trickle charge
- Electrical readings
- Battery (x2) voltage and amperage
- Charging mode
- Pressure readings
- Cut-in cut-out and continuous system pressure
Alarm contacts for remote indication* (DPDT-8A-250V.AC)
- Engine run
- Common controller trouble
- Common engine trouble
- Common pump room alarm (field re-assignable)
- H-O-A in OFF or HAND
- Free (field programmable)
Visual and audible alarms*
- AC present
- Main switch in AUTO
- Battery #1 & #2 failure
- Charger #1 & #2 failure
- Low oil pressure
- High engine temperature
- Overspeed
- Engine run
- Fail to start