Tornatech GPD Diesel Engine Fire Pump Controllers

Description

 

  • Designed to control Diesel Engine driven Fire Pumps
  • Built to the latest NFPA 20 Standards, UL Listed and FM Approved
  • Manual and Automatic Operation
  • Built in Battery Chargers
  • Pressure and event Recorder

 

Standard Features:

AC

  • 120V/1ph/50-60hz
  • 208V to 240V/1ph/50-60hz

DC

  • 12VDC
  • 24VDC

Grounding system: Negative

Battery chargers

  • Two independent fully automatic
  • 10A continuous charge
  • 500mA trickle charge  
  • Electrical readings
    • Battery (x2) voltage and amperage
    • Charging mode
    • Pressure readings
      • Cut-in cut-out and continuous system pressure

Alarm contacts for remote indication* (DPDT-8A-250V.AC)

  • Engine run
  • Common controller trouble
  • Common engine trouble
  • Common pump room alarm (field re-assignable)
  • H-O-A in OFF or HAND
  • Free (field programmable)

Visual and audible alarms*

  • AC present
  • Main switch in AUTO
  • Battery  #1 & #2 failure
  • Charger #1 & #2 failure
  • Low oil pressure
  • High engine temperature
  • Overspeed
  • Engine run
  • Fail to start